01
Design data: R and the equivalent steel thickness
We work to the fire-protection design. For each member it states the required fire-resistance rating (R) and the equivalent steel thickness.
WhyThin steel heats up faster than heavy sections. So the thickness of the fire-protection layer depends on the required R and the equivalent steel thickness. The required ratings are set by the codes (SP 2.13130) and the design; thickness follows the fire-protection design and the manufacturer’s data sheet.
ChecksThe fire-protection design, the coating data sheet, a certificate for the fire-protection material (tests to GOST R 53295), and primer/finish compatibility per the data sheet.
02
Surface preparation and primer
We clean the surface, blasting to Sa 2½ to GOST R ISO 8501-1 (ISO 8501-1) where required, remove dust and apply a primer compatible with the fire-protection coating.
WhyThe intumescent layer is held by the primer. An incompatible primer or poor preparation risks the coating peeling both in service and in a fire.
ChecksCleanliness grade, surface temperature and dew point, and primer thickness — per the manufacturer’s data sheet.
03
Fire-protection coating — layer by layer
We apply the thin-film intumescent coating in layers: by airless spray, and by brush at nodes and edges. Each layer follows the recoat drying time, up to the design dry thickness.
WhyA thick coat in one pass sags and cracks. Applying it in layers gives an even thickness, including on edges, corners and at nodes.
ChecksThe number of coats, recoat intervals and application conditions follow the manufacturer’s data sheet.
04
Wet- and dry-film thickness checks
During application we check the wet film with a comb gauge and, after drying, the dry-film thickness (DFT) with a gauge, following the measurement plan.
WhyIt is the thickness that provides the fire resistance: at a thin spot the steel will heat up sooner than the calculated time.
ChecksThe dry thickness is not below the design value, as in the fire-protection design and the manufacturer’s data sheet; plus adhesion. Areas that are too thin are built up and measured again.
05
Protective and decorative finish coat
If the design requires it, we apply a finish coat compatible with the fire-protection coating.
WhyThe finish protects the intumescent layer from moisture, UV and dirt and sets the colour. It is especially important outdoors and in damp rooms.
ChecksCompatibility and thickness of the finish follow the fire-protection manufacturer’s data sheet; the coat must be continuous, with no misses or damage.
06
How it works in a fire
When heated, the thin layer swells, increases many times in volume and turns into a porous insulating char layer.
WhyThe char layer slows the heating of the steel — the member keeps its load-bearing capacity longer, within the fire-resistance rating R in the design.
ChecksThe performance of the coating is confirmed by fire tests to GOST R 53295 — so we use only certified products.
07
Acceptance and documentation
We hand over the fire protection together with the as-built documentation.
WhyThe layers under the finish are not visible — the documents confirm that the preparation and the fire-protection thickness were completed as designed.
Checks and documents
- Concealed-works certificates to GOST R 59637: surface preparation, primer, fire-protection layer
- Work log: application conditions, materials, batch numbers
- Thickness readings per the measurement plan
- Certificates and data sheets for the fire-protection coating and the primer