Insulation, Mark III membranes and protection
Thermal and cold insulation of piping and equipment, Mark III membrane systems, covers and fittings from our own workshop, fire protection and anti-corrosion coatings — from survey and design calculations to installation and as-built documentation. HVAC for residential and commercial buildings in Moscow.
Thermal insulation of piping and equipment
A "pipe section — cladding — fasteners" system designed to last for decades: lower heat losses, burn protection for personnel, stable process conditions and fire safety.
- Stone wool pipe sections, bare or foil-faced
- Sizes: inner diameter 18–1020 mm, wall thickness 20–120 mm*
- Service temperature −180…+650 °C*, non-combustible NG (foil-faced: NG or G1)*
- Metal cladding: aluminium, stainless steel, galvanised and pre-painted steel
- Fastening: bands, self-tapping screws, rivets, beading, sealed joints
* Typical values from Russian manufacturers; actual properties per product specification and data sheet.
Thermal insulation catalogue (PDF, in Russian) · 2.6 MB ↓
Insulation layer by layer
Scroll the diagram — the steps change; for each one: what we do, why, and what we check.
Cold and cryogenic insulation
Multi-layer systems for low-temperature and cryogenic piping and equipment. The key layer is a continuous, sealed vapour barrier that prevents heat gain and condensation.
- PIR, cellular glass or elastomer layers with staggered joints
- Continuous vapour barrier, sealed joints and terminations
- Cladding on bands, no penetrations
- Build-up and thicknesses per design calculation (SP 61.13330.2012)

Covers for valves and flanges
Covers insulate gate valves, valves, flanged joints, strainers, pumps and instruments and can be removed for maintenance without damaging the insulation.
- Quick-release latches — fitting and removal without tools
- Reusable
- Stone wool or removable mattress inside
- Made to site measurements

Shaped elements
We insulate bends and nodes with the same material and thickness as the straight runs, and make complex metal jackets to site measurements for any routing and any node.
- Elbows 90°, 60°, 45°, 30° and any angle — segments cut from pipe sections, gored jacket with beading
- Tees with jacket cut along the intersection line
- Concentric and eccentric reducers
- End caps, cut-outs for supports, hangers and instrument nozzles

Mark III membrane systems
A membrane system is a thin corrugated stainless-steel membrane, insulation panels and a secondary barrier fixed directly to the load-bearing structure of an LNG tank (−163 °C). It is used in LNG carriers, FSRU/FSU, gravity-based structure (GBS) tanks and onshore tanks.
Our team has experience installing the membrane system at the Arctic LNG 2 site and working on the cargo containment of Arc7 LNG carriers at Zvezda (Bolshoy Kamen, Primorsky Krai).
- Setting-out, resin rope (mastic) application, R-PUF panel installation and alignment
- Joint filling, Triplex secondary barrier bonding
- Welding of 1.2 mm corrugated 304L membrane sheets
- Tightness testing: vacuum box, ammonia and helium tests
- As-built documentation, qualified welders and bonders
GTT, Mark III and GST are trademarks of GTT. They are mentioned for information only and do not imply partnership or licence.
Mark III membrane systems catalogue (PDF, in Russian) · 3.8 MB ↓
Mark III layer by layer
Scroll the diagram — the steps change; for each one: what we do, why, and what we check.
HVAC: heating, ventilation and air conditioning
Installation of building services for residential complexes, business centres and industrial facilities — from the bill of quantities to commissioning and handover. We bring the discipline, quality control and safety culture of large industrial sites to residential and commercial construction.
- Subcontracting for main contractors: ventilation, air conditioning, heating substations (ITP) — on your schedule and to site standards
- Installation section by section and floor by floor, in step with the building works
- Coordination with other trades: plumbing, finishes, facade
- As-built documentation in parallel with installation and daily progress reports




Ventilation
- Rectangular, circular and spiral ductwork
- Air handling units, including heat recovery
- Duct and roof fans, air terminals
- Silencers, control and non-return dampers
- Smoke control ventilation — with licensed specialists
Air conditioning
- VRF / VRV: outdoor and indoor units, refrigerant piping and refnets
- Brazing under nitrogen, pressure testing, evacuation, charging
- Chiller–fan coil: fan coils, pump groups and hydronic modules
- Split and multi-split systems, condensate drainage
Heating and substations (ITP)
- Floor-by-floor and manifold distribution
- Radiators, convectors, air curtains
- ITP: plate heat exchangers, pump groups, piping and valves
- Heat metering stations (installation), testing and flushing
Chilled water
- Chilled and heating water piping
- Chiller, dry cooler and cooling tower hook-up
- Pump groups, balancing valves
- Insulation with vapour barrier, hydraulic testing
Commissioning and handover
- Individual tests and integrated system testing
- Air balancing and aerodynamic tests
- Air and water flow adjustment, temperature and noise measurements
- Hidden-works certificates, as-built drawings, system passports
Related works from one contractor
- Thermal insulation of ducts and pipes
- Fabrication of ductwork, fittings and metal cladding
- Painting of steel structures, supports and platforms
- Fewer hand-overs between contractors — fewer schedule losses
Smoke control ventilation and fire protection of ducts are carried out with organisations holding an EMERCOM (MChS) of Russia licence where one is required for the work.
Three ways to work with us
Turnkey
Installation with supply of materials and equipment, commissioning and documentation. One responsible contractor; procurement and logistics are on us.
Client-supplied materials
You supply equipment and materials — we install and commission. Incoming inspection and material tracking, you pay for labour only.
Crews / man-hours
Installation crews and supervisors under your management: fast reinforcement of your site, flexible headcount, payment by actual hours.
HVAC step by step
Scroll the diagram — the steps change; for each one: what we do, why, and what we check.
Fire protection and anti-corrosion coatings
Two lines of protection for steel structures, piping and equipment: fire protection of steel structures and anti-corrosion protection (AKZ).


Fire protection of steel structures
We provide fire protection of steel structures at industrial plants: surface preparation, a compatible primer and application of thin-film intumescent coatings. The system is selected to achieve the fire-resistance rating required by the design (typically in the R45–R120 range), using compositions certified to GOST R 53295.
Scope of work:
- surface preparation, including abrasive blast cleaning to Sa 2½ per GOST R ISO 8501-1 (ISO 8501-1);
- priming with a primer compatible with the fire-protective coating;
- application of the thin-film intumescent coating to the specified dry-film thickness (DFT);
- dry-film thickness inspection, adhesion testing and as-built documentation, including hidden-work certificates (AOSR), in line with GOST R 59637.
Works are carried out in accordance with the licensing requirements of EMERCOM of Russia (MChS).
Preferred model: customer-supplied material, with application and inspection by our team; material supply by the contractor by separate agreement.

Anti-corrosion protection (AKZ)
We provide anti-corrosion protection of steel structures, piping and equipment using ISO 12944 coating systems, selected by the corrosivity category of the environment (C1–C5, CX; Im1–Im4 for immersion and soil) and the required durability to the first major maintenance of the coating.
Scope of work:
- surface preparation to Sa 2½ per GOST R ISO 8501-1 (ISO 8501-1), or to Sa 3 where required;
- application of the primer, intermediate and finish coats of the selected system;
- dry-film thickness (DFT) inspection of each coat, adhesion testing and as-built documentation, including AOSR.
Preferred model: customer-supplied material, with surface preparation, application and inspection by our team; material supply by the contractor by separate agreement.
We carried out painting as part of multi-discipline scopes on the Arctic LNG 2 AWP / GWP modules (2023) and at the Amur Gas Processing Plant (2025).
AKZ layer by layer
Scroll the diagram — the steps change; for each one: what we do, why, and what we check.
Fire protection step by step
Scroll the diagram — the steps change; for each one: what we do, why, and what we check.
We also do
Piping installation
Fabrication, installation and commissioning of piping at industrial plants.
From survey to handover
Survey
Site visit, measurements, list of nodes
Design
Thickness calculation, material selection, details
Prefabrication
Covers, elbows and shaped elements to measurement
Installation
Insulation and cladding by our own crews
Quality control
Step-by-step inspection and as-built documentation
Let's discuss your project
Send us the bill of quantities, technical specification or drawings and we will prepare a proposal for insulation, membrane works or coatings.